Firetuf FTP120 Fire Resistant Power Cable

Draka Firetuf Cables – Firetuf FTP120 Fire Resistant Power Cable

Draka’s Firetuf FTP120 is a Halogen Free  Low Smoke (OHLS®)   fire resistant cable(OHLS®)  that is designed to maintain circuit integrity when exposed to fire and flame.  Firetuf FTP120 is a fire resistant cable that offers 120 minute fire resistance and is manufactured with stranded copper conductors and a protective armour layer. 

The Firetuf FTP120 is a 600/1000V SWA (steel wire armoured) power cable and utilizes high performance materials in order to meet the rigorous requirements of BS8491 and the 120 minute fire resistance rating of BS8519.  Additionally Firetuf FTP120 meets the specified requirement of the constructional standard of BS7846.

Firetuf FTP120 Fire Resistant Power Cable

Firetuf FTP120 power cable maintains circuit integrity for fire safety engineering systems ( life safety, fire fighting and property protection systems). FTP120 is approved for 30, 60 and 120 minute power applications as described in BS8519

Draka’s Firetuf FTP120 power cable will satisfy the 30, 60 and 120 minute resistance requirements of all systems that require secure power supplies in the event of fire.  The Firetuf FTP120 offers enhanced fire performance over the existing generation of power cables and has a variety of applications such as automatic fire suppression facilities, fire detection and alarms, fire compartmentalisation, smoke control and ventilation, sprinkler and wet risers, ventilation and shutters and fire fighting lifts.

Firetuf FTP120 Fire Resistant Power Cable

The Building Regulations Approved Document B on fire safety was revised on 1st April 2007 and this now specifies fire performance in accordance with BS7346-6 (now superceded by BS8519:2010)

Firetuf FTP120 can be specified with confidence in meeting the demanding performance required to support modern fire engineering systems in today’s buildings.

Firetuf FTP120 fire resistant power cable: Construction  
Conductors:   Plain annealed stranded copper conductors. For sizes up to and including 35mm2 these are circular. Shaped conductors start at 50mm2 with the exception of 2 core cables where shaped conductors start at 25mm2.
Insulation:   Mica-glass fire-resistant tapes, covered by an extruded layer of cross-linked polyethylene.
Binder:   Polyester tape.
Bedding:   An extruded layer of Zero Halogen, Low Smoke (OHLS®) compound.
Armour:   Single layer of galvanised steel wires.
Sheath:   Thermoplastic Zero Halogen, Low Smoke (OHLS®) compound.

Firetuf FTP120 fire resistant power cable: Physical Characteristics  
Voltage rating (Uo/U):   600/1000V.
Operating temp:   -40°C to +90°C (The cable should not be flexed when
either the ambient or cable temperature is below 0°C).
Min. bending radius:   8 x overall diameter of cable.
Current rating:   Refer to table 4E4A or 4E4B of BS7671, ERA 69-30 pt V
Note: In the event of a fire, the increase in impedance may require consideration to the installation of larger conductor sizes, to accommodate motor starting loads and the performance of protective conductors.

Firetuf FTP120 fire resistant power cable: Standards Achieved  
Circuit integrity   BS7346-6 120 mins. / BS8491
Acid gas emission:   IEC 60754, BS EN 50267.
Flame propagation:   IEC 60332-3, BS EN 50265, BS EN 50266.
Smoke emission:   IEC 61034, BS EN 50268.


Firetuf FTP120 Fire Resistant Power Cable

Draka’s Firetuf FTP120 fire resistant power cable designs achieve the highest rating of 120 minutes (also 30 and 60 minute compliant) resistance when subjected to integrated testing involving direct impact and high pressure water spray. The details of this test are currently documented in stand alone standard BS8491.

Firetuf FTP120 fire resistant power cable Technical Data

Shaped conductors unless otherwise stated. * Circular conductors

Shaped conductors unless otherwise stated. * Circular conductors  Manufactured toBS 7846, it is tested and approved by LPCB and BASEC.

 Download the individual data sheet for Firetuf FTP120 fire resistant power cable

 Download Draka Cables Brochure to see the whole range of fire performance cables by Draka

Find your local stockist now...

Please enter your details below and we will call you as soon as possible with details of your nearest stockist

*

*

*

*